29 PRECAUTIONS ON PROGRAMMING
29.2 Interrupt from Modules
29.2
Interrupt from Modules
The following describes the precautions for interrupts from modules.
System switching in backup mode
When the old control system is switched to the new standby system
The old control system retains the interrupt factors that have occurred even after the system is switched to the new standby
system by system switching before execution of an interrupt program. After the systems are switched again, the interrupt
program of an interrupt factor that the old control system has retained will be executed.
Since the interrupt factor that has occurred on the old control system is not inherited to the new control system, the interrupt
program of an interrupt factor that has occurred on the old control system will not be executed on the new control system.
When the old standby system is switched to the new control system
The old standby system retains the interrupt factors that have occurred. After the old standby system is switched to the new
control system by system switching, the interrupt program of an interrupt factor that the old standby system has retained will
be executed on the new control system.
When the old standby system has retained multiple interrupt factors, the scan time may greatly increase.
System switching in separate mode
When the old control system is switched to the new standby system
The old control system executes the interrupt factors that the old control system has retained even after the system is
switched to the new standby system by system switching before execution of an interrupt program.
When the old standby system is switched to the new control system
The old standby system retains the interrupt factors that have occurred. The new control system executes the interrupt
program of an interrupt factor that the old standby system has retained regardless of the system switching operation.
When the operation mode is switched to the separate mode
For the control system
The control system retains the interrupt factors before switching to the separate mode. After the operation mode is switched to
the separate mode, the control system executes the interrupt programs of the interrupt factors that have occurred in the
backup mode.
For the standby system
The interrupt factors that the standby system has retained before switching to the separate mode will be discarded. Therefore,
after the operation mode is switched to the separate mode, the interrupt programs of the interrupt factors that have occurred
before switching to the separate mode will not be executed.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......