736
APPX
Appendix 1 Error Codes
2840H
File name
specification
error
• The file specified in the instruction
does not exist.
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Check the detailed information (drive/
file information) of the error by
executing module diagnostics using
the engineering tool, create the
specified file, and write it to the CPU
module. Or, set all the required files in
the CPU parameters (file setting).
Error location
information,
drive/file
information
At instruction
execution
2841H
File name
specification
error
• The program file specified in the
instruction is not set in the CPU
parameters (program setting).
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Check the detailed information (drive/
file information) of the error by
executing module diagnostics using
the engineering tool, and set the
specified program file in the CPU
parameter.
Error location
information,
drive/file
information
At instruction
execution
2842H
File name
specification
error
• A file that cannot be specified with
the instruction was specified.
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Check the detailed information (drive/
file information) of the error by
executing module diagnostics using
the engineering tool, and check the
specified file.
Error location
information,
drive/file
information
At instruction
execution
3000H
Boot function
execution error
• The boot setting in the memory
card parameters is incorrect.
Stop
• Check and correct the boot setting in
the memory card parameters.
Drive/file
information
At power-on,
at RESET
3001H
Boot function
execution error
• When the boot function was
executed, the file format
processing failed.
Stop
• Reset the CPU module and execute
the boot function again. If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module. Please consult your
local Mitsubishi representative.
Drive/file
information
At power-on,
at RESET
3003H
Boot function
execution error
• When the boot function was
executed, the file passwords did
not match.
Stop
• Check and correct the file password
settings of the transfer source and
transfer destination files.
• Delete the boot setting.
Drive/file
information
At power-on,
at RESET
3004H
Boot function
execution error
• When the boot function was
executed, the CPU built-in
memory capacity was exceeded.
Stop
• Check and correct the boot setting.
• Delete unnecessary files in the CPU
built-in memory.
• Clear the CPU built-in memory by
selecting "Clear" to "Operation Setting
at CPU Built-in Memory Boot" in the
memory card parameters, and execute
the boot function.
Drive/file
information
At power-on,
at RESET
3005H
Boot function
execution error
• When the boot function is
executed, the security key
registered in the CPU module (or
cassette) does not match the one
that locks the boot source
program.
• When the boot function is
executed, the security key is not
registered in the CPU module (or
cassette) even though the boot
source program is locked with the
security key.
Stop
• Check and correct the security key
setting.
• Delete the boot settings from the
memory card parameter.
Drive/file
information
At power-on,
at RESET
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......