830
APPX
Appendix 4 List of Special Relay Areas
SM1653
Memory copy start
Off: Not started
On: Start
• When this relay is turned from off to on, the
memory copy from the control system to the
standby system starts. Note that the
memory copy does not start as long as the
I/O number of the copy destination (standby
system CPU module: 03D1H) is not stored
when SM1653 is turned from off to on.
• Initial value is off: The memory copy has not
started.
U
RnP
SM1654
Memory copy being
executed
Off: Not executed
On: Being executed
• This relay is on during the memory copy
from the control system to the standby
system.
• This relay turns off when the memory copy
is completed.
S (Status change)
RnP
RnPSF
SM1655
Memory copy
completion
Off: Not completed
On: Completed
• This relay turns on at the completion of the
memory copy from the control system to the
standby system.
• Initial value is off: Memory copy has not
completed.
S (Status change)/U
RnP
RnPSF
SM1656
Auto memory copy
Off: Disabled
On: Enabled
This relay turns on when the automatic
memory copy is set to enable.
S (Initial)
RnP
SM1673
Tracking transfer
completion flag
Off: Transfer not completed
On: Transfer completed
• This flag is stored a result of the tracking
transfer operated in the preceding END
processing.
• The flag turns on if any of the tracking
transfers in block 1 to 64 has been normally
completed, and turns off if the tracking
transfers failed due to causes such as
tracking communication error.
S (Status change)
RnP
RnPSF
SM1679
Error reset (the other
system)
Off
On:Standby system
error reset requested
On
Off:Standby system
error reset completed
• This relay is turned from off to on to clear a
continuation error occurred in the standby
system.
• This relay turns from on to off when the
error reset has been completed.
• Initial value is off.
U/S (Status change)
RnP
RnPSF
SM1680
Error of the other system
monitoring
Off: No error
On: Error
• This relay turns on if an error occurs on
communications with the other system
when an initial processing (including when
the system is determined while waiting for
the other system starts up) or an END
processing is performed. (This relay turns
on when the bit of SD1648 turns on.)
• This relay turns off when an error is cleared.
S (Initial/every END/
system switching)
RnP
RnPSF
SM1681
Latest self-diagnostic
error (including
annunciator ON) (the
other system)
Off: No error
On: Error
• This relay turns on if a diagnostic error
occurs in the CPU module in the other
system. (The relay also turns on if an error
is detected by an annunciator.)
• The SM0 status for the CPU module in the
other system is reflected.
S (Every END)
RnP
RnPSF
SM1682
Latest self-diagnostic
error (not including
annunciator ON) (the
other system)
Off: No error
On: Error
• This relay turns on if a self-diagnostic error
occurred in the CPU module in the other
system. (The relay remains off if an error is
detected by an annunciator.)
• The SM1 status for the CPU module in the
other system is reflected.
S (Every END)
RnP
RnPSF
SM1683
Detailed information 1:
Flag in use (the other
system)
Off: Not used
On: In use
• This relay turns on when there is detailed
information 1 for an error occurred in the
CPU module in the other system.
• The SM80 status for the CPU module in the
other system is reflected.
S (Every END)
RnP
RnPSF
SM1684
Detailed information 2:
Flag in use (the other
system)
Off: Not used
On: In use
• This relay turns on when there is detailed
information 2 for an error occurred in the
CPU module in the other system.
• The SM112 status for the CPU module in
the other system is reflected.
S (Every END)
RnP
RnPSF
No.
Name
Data stored
Details
Set by (setting timing) CPU
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......