748
APPX
Appendix 1 Error Codes
3430H
Operation error
• An instruction has been executed
without setting parameters which
are required when the instruction
is executed.
Stop/
continue
• Set parameters required to execute the
instruction.
Error location
information
At instruction
execution
3440H
Operation error
• In a multiple CPU system, the
multiple CPU dedicated
instruction (the one whose symbol
starts with D(P)) was executed
when "Do Not Use" was set to
"Fixed scan communication
function" in the system
parameters ("Multiple CPU
Setting").
Stop/
continue
• Change "Fixed scan communication
function" to "Use".
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and change the multiple
CPU dedicated instruction to the one
whose symbol starts with M(P).
Error location
information
At instruction
execution
3441H
Operation error
• In a multiple CPU system, the
number of data points was
specified exceeding the multiple
CPU dedicated instruction areas
applicable for each CPU module.
Stop/
continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and change the number
of data points for the multiple CPU
dedicated instruction.
Error location
information
At instruction
execution
34A0H
Operation error
• Response data of the socket
communications instruction
cannot be created.
Stop/
continue
• Increase the request interval.
• Decrease the number of request
nodes.
• Wait for a response to the previous
request before sending the next
request.
• Correct the timeout value.
Error location
information
At END
instruction
execution
3600H
Safety system
configuration
error
■
SIL2 Process CPU, SIL2 function
module
• The SIL2 function module
controlled by the host CPU
module is not mounted to the right
of the CPU module.
• The slot right of the CPU module
is set as "Empty" in the system
parameters (I/O Assignment
Setting).
■
Safety CPU, safety function
module
• The safety function module
controlled by the host CPU
module is not mounted to the right
of the Safety CPU.
• The slot right of the Safety CPU is
set as "Empty" in the system
parameters (I/O Assignment
Setting).
Stop
■
SIL2 Process CPU, SIL2 function
module
• Mount the SIL2 function module
controlled by the host CPU module to
the right of the CPU module.
• Re-set the system parameters (I/O
Assignment Setting) so that the SIL2
function module is right of the CPU
module. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
the SIL2 function module, or the base
unit. Please consult your local
Mitsubishi representative.
■
Safety CPU, safety function module
• Mount the safety function module
controlled by the host CPU module to
the right of the Safety CPU.
• Re-set the system parameter I/O
assignment settings so that there is a
safety function module to the right of
the Safety CPU. If the same error code
is displayed again, the possible cause
is a hardware failure of the Safety
CPU, safety function module, or base
unit. Please consult your local
Mitsubishi representative.
System
configuration
information
At power-on,
at RESET
3608H
Safety system
configuration
error
• Two or more SIL2 function
modules are mounted.
Stop
• Mount only one SIL2 function module.
System
configuration
information
At power-on,
at RESET
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......