710
APPX
Appendix 1 Error Codes
1900H
Constant scan
time error
• The scan time exceeded the
constant scan time set in the CPU
parameters.
Continue
• Check and correct the constant scan
time setting.
Time
information
At END
instruction
execution
1A00H
Safety cycle
time exceeded
• Processing of the safety program,
from safety input to safety output,
did not complete within the safety
cycle time.
Continue
• Check and correct the safety cycle
time.
Time
information
At interrupt
occurrence
1A01H
Safety cycle
processing error
• Safety cycle processing was not
executed because of either of the
following reasons:
(1) The safety cycle processing
takes too much time, and the
safety cycle time was exceeded.
(2) The safety cycle processing
interrupt was not executed in the
standard program due to an
instruction with excessively long
processing time.
1A20H
Continuous
RUN time in
TEST MODE
exceeded
• The continuous RUN time in
TEST MODE was exceeded.
Continue
• Change the mode to SAFETY MODE.
TEST MODE
continuous
RUN
prevention
setting
Always
1A40H
Destination
station error in
safety
communications
• Error information has been
received from a safety
communication destination
station.
Continue
■
SIL2 Process CPU
• Check the detailed information (safety
station system configuration
information) of the error by executing
module diagnostics using the
engineering tool and check "Station
No.", "Slot No. (another station)", and
"Base No. (another station)". If the
destination station is an intelligent
device station, execute the system
monitor for the remote head module in
the station and check the error details.
■
Safety CPU
• Check the detailed information (system
configuration information) of the error
by executing module diagnostics using
the engineering tool and check the
displayed station number. If the
destination station is a remote device
station or remote I/O station, read error
history data of the destination station
by executing a command from the CC
IE Field Configuration window and
check the details of the error. If the
destination station is a master/local
station, execute the system monitor for
the station and check the details of the
error.
System
configuration
information,
safety station
system
configuration
information,
error
information of
other stations
(CC-Link IE
Field)
At interrupt
occurrence
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......