APPX
Appendix 6 List of Safety Special Relay Areas
883
A
System clock
The following is the list of safety special relay areas relating to the system clock.
Safety information
The following is the list of safety special relay areas relating to safety information.
No.
Name
Data stored
Details
Set by
(setting
timing)
CPU
SA\SM400
Always on
This relay is always on.
S (Power-on to
RUN or STOP
to RUN)
RnPSF
RnSF
SA\SM401
Always off
This relay is always off.
S (Power-on to
RUN or STOP
to RUN)
RnPSF
RnSF
SA\SM444
On at the first safety
program execution
This relay turns on at the first safety program
execution.
S (Power-on to
RUN or STOP
to RUN)
RnPSF
RnSF
SA\SM1800
ON for only the first
safety program
execution after
system switching
(standby system to
control system)
This relay turns on only the first safety cycle
processing after the standby system was switched to
the control system.
S (Status
change)
RnPSF
No.
Name
Data stored
Details
Set by
(setting
timing)
CPU
SA\SM1008
Safety refresh
communication
status of each
module (1st
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 1st
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1904) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1008 to SA\SD1015.)
S (Status
change)
RnPSF
RnSF
SA\SM1016
Safety refresh
communication
status of each
module (2nd
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 2nd
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1905) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1016 to SA\SD1023.)
S (Status
change)
RnPSF
RnSF
SA\SM1024
Safety refresh
communication
status of each
module (3rd
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 3rd
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1906) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1024 to SA\SD1031.)
S (Status
change)
RnPSF
RnSF
SA\SM1032
Safety refresh
communication
status of each
module (4th
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 4th
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1907) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1032 to SA\SD1039.)
S (Status
change)
RnPSF
RnSF
SA\SM1040
Safety refresh
communication
status of each
module (5th
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 5th
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1908) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1040 to SA\SD1047.)
S (Status
change)
RnPSF
RnSF
SA\SM1048
Safety refresh
communication
status of each
module (6th
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 6th
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1909) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1048 to SA\SD1055.)
S (Status
change)
RnPSF
RnSF
SA\SM1056
Safety refresh
communication
status of each
module (7th
module)
Off: Normal
On: Communication error
The safety refresh communication status of the 7th
CC-Link IE Field Network module (the one whose
start I/O number is stored in SD1910) is stored. (The
safety refresh communication status of each safety
connection is stored in SA\SD1056 to SA\SD1063.)
S (Status
change)
RnPSF
RnSF
ON
OFF
ON
OFF
ON
OFF
First time only
ON
OFF
First time only
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......