APPX
Appendix 1 Error Codes
767
A
40D0H
Label
communication
error
• The target CPU module does not support "Access from
External Device" of "Global Label Setting".
• Disable "Access from External Device", and then write the
data to the programmable controller again.
4100H
Any other error
• Hardware failure of the CPU module.
• Replace the CPU module.
4101H
Any other error
• Serial communication connection was executed for a
different CPU module series.
• Check the CPU module series.
4103H
Any other error
• The instruction written by online program change is incorrect
or invalid.
• Execute online program change again. Or, set the operating
status of the CPU module to STOP, and write the program.
4104H
Any other error
• An instruction(s) that cannot be executed by the CPU
module set to process mode or redundant mode is included
in the instructions targeted for online program change.
• Delete the instruction(s) that cannot be executed, and
execute the online program change function again. Or, set
the operating status of the CPU module to STOP, and write
the program.
4105H
Any other error
• Hardware failure of the CPU module internal memory
• The possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
4108H
Any other error
• The device monitor/test cannot be performed normally.
• Execute the function again. Check that the access prohibited
area is not accessed, and execute the function again.
410AH
Any other error
• The specified command cannot be executed because the
online program change is being executed.
■
When CPU Module Logging Configuration Tool is used
• The data logging where a step No. is specified as the
collection start condition or trigger condition was started
during the online program change.
• The data logging where a label (global label or local label) is
specified as the collection start condition, data collection
target, or trigger condition was started during the online
program change.
• The data logging setting file where a label (global label or
local label) is specified as the collection start condition, data
collection target, or trigger condition was written during the
online program change.
• Execute the request again after the online program change.
410BH
Any other error
• The monitor condition registration was cleared after the
online program change was executed.
• Execute the registration of monitoring condition again after
the online program change.
410CH
Any other error
• Writing to the specified data is not supported.
• Check that the version of the engineering tool used is
correct.
• Check the settings and make a correction.
410EH
Any other error
• When the execution status of the online program change is
in error, the online program change command was issued.
• Issue the online program change cancel command, and
execute the function again.
410FH
Any other error
• During the execution of the online program change function,
the cancel command was issued by the same request
source.
• Issue the command again after the currently-performed
processing ends.
4110H
CPU module
error
• The request cannot be executed because the CPU module
is in a stop error state.
• Reset the CPU module and execute the request again.
4111H
CPU module
error
• The request cannot be executed because the other CPU
modules, except the host CPU module, have not yet started
in a multiple CPU system.
• Execute the request again after all the other CPU modules
have started.
4121H
File related error
• The specified drive (memory) or file does not exist.
• Execute again after checking the specified drive (memory)
or file.
4122H
File related error
• The specified drive (memory) or file does not exist.
• Execute again after checking the specified drive (memory)
or file.
4123H
File related error
• The specified drive (memory) is abnormal.
■
When CPU Module Logging Configuration Tool is used
• The data logging was started to the memory having an error.
• Initialize the memory, and restore the drive (memory) to its
normal state.
4124H
File related error
• The specified drive (memory) is abnormal.
• Initialize the memory, and restore the drive (memory) to its
normal state.
4125H
File related error
• The specified drive (memory) or file is performing
processing.
• Execute again after a while.
4126H
File related error
• The specified drive (memory) or file is performing
processing.
• Execute again after a while.
4127H
File related error
• File password mismatch
• Execute again after checking the file password.
4128H
File related error
• File password mismatch with copy destination
• Execute again after checking the file password.
4129H
File related error
• The request cannot be executed since the specified drive
(memory) is ROM.
• Execute again after changing the target drive (memory).
Error
code
Error name
Error details and cause
Action
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......