APPX
Appendix 1 Error Codes
759
A
3E00H
Operation circuit
error
■
CPU module, SIL2 function
module, safety function module
• An error has been detected in the
CPU module, SIL2 function
module, or safety function module.
■
Redundant function module
• An error has been detected in the
redundant function module.
Stop
■
CPU module, SIL2 function module,
safety function module
• Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
■
Redundant function module
• Reset the CPU module.
• If the error code is displayed again
even after taking an action, please
consult your local Mitsubishi
representative.
Failure
information
At power-on,
at RESET
3E01H
Operation circuit
error
• An error has been detected in the
CPU module, SIL2 function
module, or safety function module.
Stop
• Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Failure
information
At END
instruction
execution, at
power-on, at
RESET
3E10H
Circuit error
• An error has been detected in the
CPU module, SIL2 function
module, or safety function module.
Stop
• Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Failure
information
At END
instruction
execution, at
power-on, at
RESET
3E11H
3E12H
At power-on,
at RESET
3E20H
Program
execution error
• The entire program was executed
without executing the END
instruction.
Stop
• Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Failure
information
At END
instruction
execution
3E22H
Program
execution error
• The FB/FUN program did not
complete successfully.
At instruction
execution
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......