Address
Name
Data stored
Details
Set by
(setting
timing)
Un\G1024
Total number of
connected stations
Total number of
connected stations
The total number of connected stations set in parameter is stored.
Range: 1 to 16
S (Initial)
Un\G1025
Reserved station
specification status
Reserved station
specification status
The reserved station specification status of the slave station specified
in parameter is stored. (0: Not specified, 1: Specified)
b0: Reserved station specification status
b1 to b15: Empty (fixed to 0)
The station number that is specified as a reserved station can be
checked in 'Reserved station specification status of each station'
(Un\G1026).
S (Initial)
Un\G1026
to
Un\G1029
Reserved station
specification status of
each station
Reserved station
specification status of
each station
The reserved station specification status is stored using the following
bit pattern. (Off: Other than the reserved station, On: Reserved station)
The numbers in the figure indicate station numbers.
(Condition)
• Only the bit of the start station number turns on.
• The status is not stored for the station numbers after the maximum
station number.
S (Initial)
Un\G1030
Link scan information
Group No.1 maximum
link scan
The maximum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1031
Group No.1 minimum link
scan
The minimum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1032
Group No.1 current link
scan
The current link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1034
Group No.2 maximum
link scan
The maximum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1035
Group No.2 minimum link
scan
The minimum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1036
Group No.2 current link
scan
The current link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1038
Group No.3 maximum
link scan
The maximum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1039
Group No.3 minimum link
scan
The minimum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1040
Group No.3 current link
scan
The current link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1042
Group No.4 maximum
link scan
The maximum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1043
Group No.4 minimum link
scan
The minimum link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1044
Group No.4 current link
scan
The current link scan time value during cyclic transmission is stored.
(Unit: ms)
S (Status
change)
Un\G1050
Diagnostic information
display request
Diagnostic information
display request
After the END instruction of the scan where the bit 0 is turned off and
on is executed, the diagnostic information of a slave station specified in
'Diagnostic request information' (Un\G1051) is read to Un\G1052 to
Un\G1077.
When reading of the diagnostic information has completed at END
processing, 0 is stored.
b0: Diagnostic information display request
b1 to b15: Empty (fixed to 0)
S (Status
change)
b0
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Un\G1026
Un\G1027
Un\G1028
Un\G1029
b0
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......