37 FUNCTIONS
37.8 Switching Safety Operation Mode
657
37
Safety operation mode switching conditions
The following table lists the conditions under which the safety operation mode can be changed.
How to switch the safety operation mode
The safety operation mode can be switched using the engineering tool.
[Online]
[Safety PLC Operation]
[Switch Safety Operation Mode]
The execution target of mode switching can be specified from the following options.
For details, refer to the following.
GX Works3 Operating Manual
Safety operation mode
switching direction
Condition
TEST MODE
SAFETY MODE
The user who operates the mode switching has "Developers" access level or higher, and is currently logged on.
The safety operation mode is currently set to the TEST MODE.
The SIL2 Process CPU operating status is other than RUN.
The SIL2 Process CPU is not in the process of changing operating status.
The following files held by the engineering tool, SIL2 Process CPU, and SIL2 function module match.
• Safety CPU parameter
• Safety module parameter
• Safety program
• Safety FB file
• Safety global label setting file
• Standard/safety shared label setting file
The following files are not being written from another engineering tool.
• Safety CPU parameter
• Safety module parameter
• Safety program
• Safety FB file
• Safety global label setting file
• Standard/safety shared label setting file
SAFETY MODE
TEST MODE
The user who operates the mode switching has "Developers" access level or higher, and is currently logged on.
The safety operation mode is currently set to SAFETY MODE or SAFETY MODE (wait-for-restart).
The SIL2 Process CPU is not in the process of changing operating status.
Execution target specification
Operation
Currently Specified Station
Switches the safety operation mode for the CPU module specified in the transfer setup.
Specify Both Systems
Switches the safety operation modes for the CPU modules of both systems.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......