APPX
Appendix 1 Error Codes
709
A
1260H
Multiple CPU
synchronization
processing error
• The execution interval of a
synchronous interrupt program
has exceeded the set value.
• The multiple CPU synchronous
interrupt program (I45) did not
complete within the multiple CPU
fixed scan communication cycle.
Continue
• Check the detailed information (time
information) of the error by executing
module diagnostics using the
engineering tool, check the time
setting, and take the following actions:
(1) Check and correct the processing of
the interrupt program (I45) so that it
can be completed within the period
specified in the fixed scan interval
setting.
(2) Check and correct the fixed scan
interval setting value.
Time
information
At interrupt
occurrence
1262H
• The program execution section of
a synchronous interrupt program
has been exceeded.
• The multiple CPU synchronous
interrupt program (I45) did not
complete within the program
execution section.
1800H
Annunciator ON
• The annunciator (F) on status has
been detected.
Continue
• Check the detailed error information
(annunciator information) by executing
module diagnostics using the
engineering tool, and correct the
program corresponding to the
displayed annunciator number.
Error location
information
and
annunciator
information
At instruction
execution
1810H
Operation
continuation
error
• The PALERT(P) instruction was
executed.
Continue
• Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool and check the
corresponding program - one that
outputs the program error code.
Error location
information
and program
error
information
At instruction
execution
1811H
Control CPU
error
• An error has been detected in the
CPU module.
Continue
• Check the error details by executing
module diagnostics using the
engineering tool and take an action.
Always
1812H
Module error
• Tracking communications could
not be performed successfully due
to an error in the redundant
function module.
Continue
• The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
• Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Always
1830H
Receive queue
full
• The number of transient receive
request exceeded the upper limit
of simultaneously processable
requests.
Continue
• Reduce the frequency of transient
transmission, and perform
transmissions again.
• Increase the frequency of transient
transmission by using the COM
instruction.
Always
1831H
Receive
processing error
• Transient reception failed.
Continue
• Reduce the frequency of transient
transmission, and perform
transmissions again.
System
configuration
information
Always
1832H
Transient data
error
• Too much transient transmission
processing exists and transient
transmission cannot be
performed.
Continue
• Correct the number of transient
transmission executions.
Always
1845H
Transient data
buffer full
• Too much transient transmission
processing exists and transient
transmission cannot be
performed.
Continue
• Correct the number of transient
transmission executions.
Always
1860H
Network error
• Tracking communications stopped
due to an error in the network or in
the redundant function module.
Continue
• Check the network status by executing
module diagnostics using the
engineering tool and take an action.
• If the error code is displayed again
even after taking an action, please
consult your local Mitsubishi
representative.
Always
1861H
Tracking
communication
error
• Tracking communications could
not be performed successfully due
to an error in the network or in the
redundant function module.
Error
code
Error name
Error details and cause
Stop/
continue
Action
Detailed
information
Diagnostic
timing
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......