26 BASIC CONCEPT
26.7 Determination of Control System/Standby System
When starting up the previous control system as the control
system
In a redundant system, the system A is always specified as the control system when both systems are started up
simultaneously.
Even though both systems are temporarily powered off due to a power failure or other causes while the system B is operating
as the control system, the system A is started up as the control system when both systems are powered on again.
To start up the system B that was the previous control system as the control system again, create a program that uses
SM1636 (Previous control system identification flag).
For a system where a network module has been mounted, execute the SP.CONTSW instruction after a network module on
the other system is started up.
Program example
Executing a system switching instruction when the CPU module in the system A is set to the RUN state for the first time
switches the system B to the control system.
Turn on SM1646 (System switching by a user) in advance.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......