10 TEST FUNCTION
10.2 Device test with execution conditions
167
10
■
Online change (ladder block) (with deleting instruction)
When an instruction is deleted by the online change (ladder block), registrations of the device test with execution conditions
for the deleted instruction and for the instruction immediately after the deleted instruction are disabled.
In the following example, an instruction is deleted by the online change (ladder block). In this case, when the device test with
execution conditions is registered to the instruction immediately after the deleted instruction, the relevant registrations are
disabled upon the execution of the online change (ladder block).
However, when an instruction to be deleted is adjacent to an instruction to be changed, registration of the device test with
execution conditions of the instruction immediately after the instruction to be deleted is not disabled.
In the following example, an instruction to be deleted is adjacent to an instruction to be changed. Therefore, even when the
device test with execution conditions is registered to the instruction immediately after the instruction to be deleted, the
relevant registration is not disabled by the execution of the online change (ladder block).
(1) The registration of the device test with execution conditions is disabled because the instruction is located immediately after the deleted instruction.
(2) The registration of the device test with execution conditions is disabled because the instruction where it is registered is deleted.
(1) Although this instruction is located immediately after the deleted instruction, the registration of the device test with execution conditions is not disabled
because the deleted instruction is adjacent to the changed instruction.
(2) The registration of the device test with execution conditions is disabled because the instruction where it is registered is changed.
(3) The registration of the device test with execution conditions is disabled because the instruction where it is registered is deleted.
(2)
(1)
Registration 1
Registration 2
Registration 3
Before
Registration 1
Registration 2
Disabled
Disabled
Registration 3
After
AND M15 is deleted.
(3)
(2)
(1)
Registration 1
Registration 2
Registration 3
Before
Registration 1
Registration 2
Disabled
Disabled
Registration 3
After
AND X11 is changed to AND X16.
AND M15 is deleted.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......