26 BASIC CONCEPT
26.7 Determination of Control System/Standby System
26.7
Determination of Control System/Standby System
This section describes how to determine which system is the control system and the other is the standby system.
When starting up both systems simultaneously
The following describes the method of determining the system types of when both systems are started up simultaneously.
How to determine the system types
A control system or standby system is determined when both the systems are powered off and on or the CPU module is reset
and then ready for tracking communications.
■
When both systems are started up simultaneously
When both systems are started up simultaneously, the system A operates as the control system and the system B as the
standby system.
"Simultaneously" here means that one CPU module is started up within three seconds after the other CPU module is started.
■
When one of the system A and system B is started up first
When one of the systems is started up first, the system will wait for the start-up of the other system in three seconds. (
Page 412 The system waiting for the start-up of the other system)
When communications for both systems are established, system A operates as the control system and system B as the
system B.
Check method
Check the LED of each redundant function module to check the status of the control system/standby system.
Users can check the status of the control system/standby system with the engineering tool. (
GX Works3
Operating Manual)
• System monitor
• Monitor status bar
Precautions
■
If the system A/B settings have not been set for both systems or the same system setting has
been set for both systems
If the system A/B settings have not been set for both systems or the same system setting has been set for both systems, a
stop error occurs. To determine the control system and standby system, properly set the system A/B settings for both
systems.
■
If both systems are restarted when a stop error has occurred on the standby system (system
A)
If both systems are restarted simultaneously in a system where the system A operates as the standby system due to a stop
error and the system B normally operates as the control system, a stop error may occur on both systems.
If the stop error cause of the system A is a program error, a stop error occurs on the system A again after the systems are
restarted. Even if the system B normally operates as the control system before the restart, a stop error occurs on the system
B if a mismatch between files is detected in the system consistency check after the restart. As a result, a stop error occurs on
both systems.
In this case, eliminate the cause of the error that has occurred on the system A and reset and restore both systems.
System status
LED of the redundant function module
Control system
Standby system
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......