APPX
Appendix 8 Buffer Memory
897
A
*1 Data is stored at END processing where the value is changed.
*2 When the count exceeds 65535, counting is continued from 1 again.
*3 A slave station specified is being disconnected, the information immediately before the disconnection is stored.
Un\G1053
to
Un\G1064
Diagnostic information 1
Diagnostic information 1
When 1 (valid) is stored in b0 to b7 of Un\G1052, the number of
occupied stations, group number, IP address, the accumulated number
of timeouts, and the accumulated number of disconnection detection
are stored. When 0 (invalid) is stored in b0 to b7 of Un\G1052, 0 is
stored.
■
Un\G1053: Number of occupied stations
■
Un\G1054: Group number
■
Un\G1055: IP address (lower)
■
Un\G1056: IP address (upper)
1 to 4: First octet to fourth octet
When the IP address has not been set in the parameter, 0 is stored.
■
Un\G1063: Accumulated number of timeouts
After the END instruction of the scan where the bit 0 of 'Diagnostic
information display request' (Un\G1050) is turned off and on is
executed, the accumulated number of timeouts that occurred in a slave
station specified in 'Diagnostic request information' (Un\G1051) is
stored.
• 0: No timeouts
• 1 to 65535: Number of timeouts (accumulated number)
■
Un\G1064: Accumulated number of disconnection detection
After the END instruction of the scan where the bit 0 of 'Diagnostic
information display request' (Un\G1050) is turned off and on is
executed, the accumulated number of disconnections that detected in
a slave station specified in 'Diagnostic request information' (Un\G1051)
is stored.
• 0: No disconnections
• 1 to 65535: Number of disconnection detection (accumulated
number)
S (Status
change)
Un\G1068
to
Un\G1077
Diagnostic information 2
Diagnostic information 2
When Diagnostic information 2 is valid (1 is stored in b8 to b15 of
Un\G1052), the manufacturer code, model code, device version,
module information, error code, and detailed module information are
stored. When Diagnostic information 2 is invalid (0 is stored in b8 to
b15 of Un\G1052), 0 is stored.
■
Un\G1068: Manufacturer code
■
Un\G1070: Model code (lower)
■
Un\G1071: Model code (upper)
■
Un\G1072: Device version
■
Un\G1074: Module information
■
Un\G1075: Error code
■
Un\G1076: Detailed module information (lower)
■
Un\G1077: Detailed module information (upper)
S (Status
change)
Address
Name
Data stored
Details
Set by
(setting
timing)
3
1
4
2
b15 to b8
b7 to b0
Un\G1055
Un\G1056
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......