11 DATA LOGGING FUNCTION
11.5 States of the Data Logging Function
11.5
States of the Data Logging Function
The data logging function has the data logging state. The data logging state can be checked by CPU Module Logging
Configuration Tool. (
Page 988 Logging status and operation)
Data logging states
The following table lists all the possible data logging states.
*1 CPU Module Logging Configuration Tool displays "Saving the logging data" as the data logging state until saving of collected data
completes. After the completion, the state changes to each of three states.
*2 The execution of another function includes:
Execution of data logging with the same trigger conditions (trigger conditions = the specified conditions)
Auto logging
Online change
Data logging states
Description
Stop
Data logging settings are unregistered and data collection is inactive.
Stop (after collection)
Transition from "Collection completed" to "Stop" has occurred due to the execution of another function
.
Stop (after error)
Transition from "Error" to "Stop" has occurred due to the execution of another function
.
RUN waiting (no collection)
Data collection has not yet begun because the operating status of the CPU module is not in the RUN state.
Start waiting (no collection)
Data collection is inactive, waiting for the start command.
Pause
Data logging is suspended and data collection has not yet been started. (The data logging settings remain intact.)
Condition waiting (no collection)
Data logging settings are registered and waiting for the first collection timing.
Collecting
Continuous logging is active and collecting data.
Trigger waiting (Collecting before trigger)
Data logging settings are registered, data collection is being performed, and waiting until the trigger condition is
met.
Collecting after trigger
Trigger logging is active and collecting data after the trigger condition is met.
Collection completed
• Continuous logging: Data collection has finished upon reaching "Number of files to be saved" specified as part
of the "Stop" setting configured in "Operation when exceeds the number of files". (The data logging settings
remain intact.)
• Trigger logging: Trigger logging has finished collecting data as much as the specified number of records. (The
data logging settings remain intact.)
Error
Data logging has failed due to the occurrence of an error.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......