542
33 FUNCTIONS
33.3 Safety Diagnostic Function
33.3
Safety Diagnostic Function
The following lists self-diagnostic functions specific to the Safety CPU.
*1 Self-diagnostics is performed in both Safety CPU and safety function module.
Item
Description
Diagnostic timing
Error code
Memory diagnosis
RAM diagnosis
Detects errors occurring at program memory,
device memory, and memory used by the system.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3C20H, 3C21H,
3C22H, 3C2FH,
3C33H
F/W diagnosis
Diagnoses whether the firmware stored in the
ROM is corrupt.
• When power is turned off and
on
• When the CPU module is reset
3C10H
Program diagnosis
Operation circuit
diagnosis
Detects errors at operation circuits used to
operate safety programs.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3C15H
File verification
Detects errors in stored safety programs and
safety parameters.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
2180H, 36E1H,
3C33H, 3C34H
Diagnoses whether safety programs and safety
parameters stored in both the Safety CPU and
safety function module are the same.
• When power is turned off and
on
• When the CPU module is reset
2180H, 3640H
Operation result
verification
Output data
verification
Verifies output results calculated in the Safety
CPU and safety function module.
When executing safety cycle
processing
3E60H
System diagnosis
Time monitoring
Monitors the execution status of the respective
Safety CPU and safety function module
processing.
Always
3E61H
Microcomputer
diagnosis
Detects microcomputer internal register errors.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3C00H, 3C01H
Power supply
voltage monitoring
Power supply voltage
monitoring
Detects voltage errors to prevent operation with
voltage outside the guaranteed operating range.
Always
(Performs a
shutdown.)
Power supply voltage
monitoring/shutdown
circuit diagnosis
Monitors whether the circuit monitoring the power
supply voltage and circuit used to perform
shutdown are functioning properly.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3E10H, 3E11H
Reset circuit
monitoring
Reset circuit
monitoring diagnosis
Diagnoses whether the reset has been performed
correctly.
• When power is turned off and
on
• When the CPU module is reset
3E12H
Clock stop
detection
Clock diagnosis
Detects clock errors (frequency errors).
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3C16H
CRC calculation
circuit diagnosis
CRC calculation
circuit diagnosis
Diagnoses whether the CRC calculation circuit is
capable of correctly calculating CRC.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3E01H
Module
Module OS diagnosis
Verifies whether the Safety CPU and safety
function module are functioning normally without
running out of control.
• When power is turned off and
on
• When the CPU module is reset
• When END processing is
performed
3C11H, 3C17H
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......