26 BASIC CONCEPT
26.2 System Switching Between the Control System and Standby System
407
26
26.2
System Switching Between the Control System
and Standby System
In a redundant system, data link is performed between the redundant function modules connected with tracking cables and
data required for operation is transferred (tracking transfer) at every scan from the control system to the standby system. If an
error occurs in the control system, the standby system will function as the new control system and continue the control using
the data that the system has received.
For details on the system switching, refer to the following.
26.3
System Consistency Check
In a redundant system, whether both systems have the same configuration is checked to switch the system and continue the
operation without causing a system failure. (
Page 475 System Consistency Check)
26.4
Operation Mode of the Process CPU
A Process CPU operates in one of the following two modes.
Process mode
Use this mode when a redundant system is not built. When "Mode" has been set to "Process" at project creation with the
engineering tool, the Process CPU is started up in the process mode.
Redundant mode
Use this mode when a redundant system is built. When "Mode" has been set to "Redundant" at project creation with the
engineering tool, the Process CPU is started up in the redundant mode. (
Set the redundant mode for both systems in a redundant system.
(1) The control system is operating without
errors. (Data is transferred to the standby
system from the control system at every
scan.)
(2) A stop error occurs on the control system.
(3) The standby system now functions as the
new control system and continues the
control using the data that the system has
received.
(1)
(3)
(2)
System A
Control system
System B
Standby system
System A
Control system → Standby system
System B
Standby system → Control system
Stop error
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......