628
37 FUNCTIONS
37.2 Tracking Transfer
Tracking transfer setting
The following describes the CPU parameters related to tracking transfer.
[CPU Parameter]
[Redundant System Settings]
[Tracking Setting]
Window
Displayed items
Set "Detailed setting" of "Tracking Device/Label Setting" for the following purposes.
• To shorten a tracking transfer time
• To add tracking data, such as the file register (ZR)
• To transfer each data set individually
When "Process Control Extension Setting" is enabled
The tracking transfer setting is automatically configured in detailed settings. The range of the file register specified to the
system resource of the optional process control extension setting is registered to the tracking block No.64.
Since the other devices are not automatically registered, specify the other tracking block numbers for those devices. The
devices and their ranges set in "Device/Label Memory Area Setting" can be input in a batch by clicking the [Device Setting
Reflection] button in the "Global Device Setting" window. (
Page 631 Global device setting)
Item
Description
Setting range
Default
Signal Flow Memory
Tracking Setting
Set whether to transfer the signal flow memory or not. (
Tracking transfer setting for the signal flow memory)
• Do Not Transfer
• Transfer
Transfer
Tracking Device/Label
Setting
Set "Transfer collectively" or "Detailed setting" for devices or labels to be
transferred.
• When "Transfer collectively" is set, global devices, local devices, global
labels, and local labels are assigned to the tracking block No.1 and
automatically transferred. (
• When "Detailed setting" is set, detailed settings can be configured in
"Tracking Block No.1 Auto Transfer Setting" and "Device/Label Detailed
Setting".
• Transfer collectively
• Detailed setting
Transfer collectively
Tracking Block No.1
Auto Transfer Setting
Set whether to automatically transfer the tracking block No.1 or not. (
Page 626 Tracking block and tracking trigger)
• Do Not Transfer
Automatically
• Transfer
Automatically
Transfer Automatically
Device/Label Detailed
Setting
Set devices and labels to be transferred. (
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......