26 BASIC CONCEPT
26.7 Determination of Control System/Standby System
■
I/O signals
The following table lists the details on the I/O signals.
■
Setting time of the external on delay timer
For the on delay timer for starting up the control system, set the setting time longer than the time duration of the start-up of
both systems.
*1
The following shows a reference setting time.
• Setting time of the external on delay timer = Start-up time of the CPU Time lag of power-on +
Check the start-up time with the actual system and adjust the setting time (
) because the start-up time of the CPU module
depends on the system configuration.
*1 If the setting time of the external on delay timer is shorter than the above, a stop error may occur on one system even though tracking
cables are connected properly because turning on X20 (Control System Start-up Setting (Input (X))) starts this program example.
Parameter settings
The following shows parameter settings.
■
System parameter
Set the system parameter according to the system configuration in "I/O Assignment Setting".
■
CPU parameter (program settings)
Set this program example (INITIAL in this example) in "Program Setting" as follows.
Device No.
Signal name
X20
Control System Start-up Setting (Input (X))
With the on delay timer wired externally, X20 turns on and the CPU module starts as the control system after a certain time.
X21
Starting up (other system)
X22
Control system (other system)
Y31
Starting up (own system)
Y32
Control system (own system)
• Set "INITIAL" for "Execution Type".
• Set "Control System Execution" in "Both Systems Program Executions Setting".
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......