User Manual Of EL7-EC** AC Servo
98
Activation
Immediate
If Pr5.12 = 0, overload level = 115%
Use only when overload level degradation is needed.
Pr5.13
Label
Overspeed level settings Mode
F
Range
0~10000 Unit
RPM
Defaul
t
0
Index
2513h
Activation
Immediate
If motor speed exceeds Pr5.13, Er1A0 might occur.
When Pr5.13 = 0, overspeed level = max. motor speed x 1.2
Pr5.15
Label
I/O digital filter
Mode
F
Range
0~255
Unit
0.1ms
Defaul
t
10
Index
2515h
Activation
Immediate
Digital filtering of I/O input. Overly large value set will cause control delay.
Pr5.17
Label
Counter clearing input
mode
Mode
F
Range
0~4
Unit
-
Defaul
t
3
Index
2515h
Activation
Immediate
To set the clearing conditions for deviation counter clearing input signal.
Set value
Condition
0/2/4
Invalid
1
Always clear
3
Clear only once
Pr5.20
Label
Position unit settings
Mode
PP
HM
CSP
Range
0~2
Unit
— Default
2
Index
2520h
Activation
Disable
Set value
Unit
0
Encoder unit
1
Command unit
2
0.0001rev
Command unit: Pulse from host
Encoder unit: Pulse from encoder
Pr5.20 only changes the unit use on host tracing function, has no relation with any position
related parameters.