User Manual Of EL7-EC** AC Servo
97
Pr5.09
Label
Main power-off detection time
Mode
F
Range
50~2000
Unit
ms
Default
50
Index
2509h
Activation
Immediate
To set duration time for detection of main power-off or low voltage supply.
Pr5.11
Label
Servo braking torque setting
Mode
F
Range
0~500 Unit
%
Defaul
t
0
Index
2511h
Activation
Immediate
To set torque limit for servo braking mode.
If Pr5.11 = 0, use torque limit as under normal situation.
Between max. torque 6072 and Pr5.11, actual torque limit will take smaller value.
Pr5.12
Label
Overload level
setting
Mode
F
Range
0~115 Unit
% Default
0
Index
2512h
Pr5.10
Label
Servo-off due to
alarm mode
Mode
F
Range
0~2
Unit
-
Default
0
Index
2510h
Activation
After restart
To set servo driver disable mode and status if alarm is triggered.
Alarm type 2:
Set value
Explanation
Mode
Status
0
Servo braking
Dynamic braking
1
Free stopping
Dynamic braking
2
Dynamic braking
Dynamic braking
3
Servo braking
Free-run
4
Free stopping
Free-run
5
Dynamic braking
Free-run
Alarm type 1:
Set value
Explanation
Mode
Status
0
Dynamic braking
Dynamic braking
1
2
3
Servo braking
Free-run
4
Free stopping
Free-run
5
Dynamic braking
Free-run