10. d14rg Regenerative load factor d15oL Overload factor
Regenerative load factor
(
Er120 might occur, if the value increases indefinitely
)
50
Load factor in
regenerative resistance
circuit [%]
d14rg
S
Overload factor
(
Er100 might occur, if the value increases indefinitely
)
50
Load ratio as with rated
load
d15oL
S
11
、
d16Jr Inertia ratio
250
Actual inertia ratio during
motion [%]
d16Jr
S
Please refer to Inertia Measuring section for detailed explanations.
12
、
d17Ch Motor not running cause
Error code of motor
not running
d17Ch
S
cP 0
“d17Ch” Motor No Running Cause - Codes & Descriptions
Display Code
Description
Content
cP 1
DC bus undervoltage
/
cP 2
No SRV-ON signal
Servo-ON input (SRV-ON) is not connected to
COM-
cP 3
POT/NOT input valid
Pr5.04 = 0, POT is in open circuit, velocity
command is in positive direction
NOT is in open circuit, velocity command is in
negative direction