User Manual Of EL7-EC** AC Servo
66
Pr0.06
Label
Command polarity
inversion
Mode
F
Range
0 ~ 1
Unit
—
Default
0
Index
2006h
Activation
After restart
Used to change the rotational direction of the motor.
Set value
Details
0
Polarity of the command is not inversed. The direction of rotation is
consistent with the polarity of command.
1
Polarity of command is inversed. The direction of rotation is opposite
to the polarity of command.
Note: Rotational direction of the motor is recommended to be set through object dictionary 607E.
However, Pr0.06 has higher priority than object dictionary 607E. 607E only takes effect when
Pr0.06 = 0.
Pr0.07
Label
Probe signal polarity
settings/Command pulse
input mode settings
Mode
F
Range
0 ~ 3
Unit
—
Default
3
Index
2007h
Activation
After restart
Probe signal polarity settings take effect when Pr0.01 = 9
Set value
Details
0
Probe 1 & 2 polarity inversion
1
Probe 2 polarity inversion
2
Probe 1 polarity inversion
3
No polarity inversion for probe 1 & 2
If Pr0.01
≠
9, Pr0.07 = Command pulse input mode settings.
Command pulse input
Command
Polarity
inversion
(Pr0.06)
Command pulse
input mode
settings
(Pr0.07)
Command Pulse
Mode
Positive signal
Negative signal
【
0
】
0
or
2
90°phase
difference
2 phase pulse
﹙
Phase A+ Phase
B
)
1
CW pulse sequence
+
CCW pulse
sequence