User Manual Of EL7-EC** AC Servo
109
1
:
Motor decelerates and stops through 609A
CST
0
:
To stop motor through Pr5.06, 5.06 = 0(Emergency stop), 5.06=1(Free stop)
1
:
Motor decelerates and stops through 6087
Index
605Dh
Label
Pause-stopping mode
selection
Unit
-
Structure
VAR Type
INT 16
Access
RW
Mapping -
Mode
F
Range
1~3
Default 1
When control word – pause sets decelerating, stopping mode. Also suitable for deceleration mode
settings during mode switching
PP, CSP, CSV, PV
1
:
Motor decelerates and stops through 6084. Status: Operation enabled, axis enabled.
2
:
Motor decelerates and stops through 6085. Status: Operation enabled, axis enabled.
3
:
Motor decelerates and stops through 60C6. Status: Operation enabled, axis enabled.
HM
1
:
Motor decelerates and stops through 609A. Status: Operation enabled, axis enabled.
2
:
Motor decelerates and stops through 6085. Status: Operation enabled, axis enabled.
3
:
Motor decelerates and stops through 60C6. Status: Operation enabled, axis enabled.
CST
1, 2
:
Motor decelerates and stops through 6087. Status: Operation enabled, axis enabled.
3
:
Motor decelerates and stops through torque = 0. Status: Operation enabled, axis enabled.
Index
605Eh
Label
Alarm - stopping mode
selection
Unit
-
Structure
VAR Type
INT 16
Acces
s
RW
Mapping -
Mode
F
Range
0~2
Default 0
Select stopping mode when servo alarm (Err 8xx) occurs.
PP, CSP, CSV, PV
0
:
Select motor stopping mode according to alarm properties. Status: Fault, axis disabled.
1
:
Motor decelerates and stops through 6084. Status: Fault, axis disabled.
2
:
Motor decelerates and stops through 6085. Status: Fault, axis disabled.
HM
0
:
Select motor stop by the alarm attribute for emergency stop, the fault state and disable
1
:
After the 609A motor is decelerated and stopped,, the fault state and disable
2
:
After the 6085 motor is decelerated and stopped, the fault state and disable
CST
0, 1
:
Select motor stop by the alarm attribute for emergency stop, the fault state and disable
2
:
After the 6087 motor is decelerated and stopped, the fault state and disable
When other alarms, i.e. drive-side alarms:
Select motor stop by the alarm attribute for emergency stop, the fault state and disable