9.2.2 Positioning and speed of poor precision (incorrect operation)
Situation
Possible cause
Check/Treatment
Completion of operation
on the way to home
return.
In the home return of our standard
specification, the actuator is first
pressed to the mechanical end, moved
oppositely, and subject to positioning
stop at the home position. Therefore,
the product may judge as the
mechanical end even though it is still on
the way when the load is large and
interfere with surrounding object.
1) A load exceeding its rating weight is
installed on the actuator.
2) It is touched to interference in the way
of the run.
3) Torsion stress is applied to guide due
to improper fixing method of the
actuator or uneven fastening of bolts.
4) The sliding resistance of the actuator
itself is large.
1) Reduce the load.
2) Remove the interference.
3) Loosen the fixing bolts once and
check whether the slider can
move smoothly.
If the slider can move smoothly,
check if there is a deformation on
the attached surface, and install
the actuator again following the
instructions stated in Instruction
Manual.
4) Please contact IAI.
Shocks at start and/or
stop.
Acceleration/deceleration is set too
high.
Decrease the settings of
acceleration/deceleration.
Overshoot during
deceleration to stop.
The load inertia is large.
Decrease the setting of
deceleration.
Positioning of poor
precision.
Uneven speed during
movement.
Acceleration/deceleration
not smooth (bad speed
response).
[Refer to 8.3 Servo Adjustment.]
Positioning at a position
different from that of
commanded position No.
For remote I/O mode, the start signal
CSTR after the position number
command is too early, or input at the
same timing.
Note Inputting at the same timing is
available for Fieldbus Type.
(Excluding remote I/O mode)
The stop position may be set for
another purpose. Make sure to
complete the reading of the position
numbers to this controller before
inputting the start signal.
Complete signal PEND is
not output even though
positioning process is
completed.
Start signal CSTR is not turned OFF.
Make the start signal CSTR turned
OFF before completing the
positioning process by the turn-off
of positioning complete signal
PEND after starting operation, and
so on.
Chapter 9
Troubleshooting
Содержание MCON-C
Страница 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Страница 2: ......
Страница 22: ...12 International Standards Compliances MCON with the following overseas standard RoHS Directive CE Marking UL ...
Страница 48: ...38 Chapter 1 Specifications Check ...
Страница 264: ...254 Note 1 blinking Note 2 single flash Note 3 double flash Timing of LED flashing 3 10 Fieldbus Status LEDs ...
Страница 268: ...258 3 10 Fieldbus Status LEDs ...
Страница 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Страница 278: ...268 Chapter 5 Collision Detection Feature ...
Страница 284: ...274 Chapter 6 Power saving Function ...
Страница 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Страница 358: ...348 Chapter 9 Troubleshooting ...
Страница 368: ...358 4 TP adapter and accessories 1 TP adapter external dimensions RCB LB TGS Chapter 10 Appendix ...
Страница 474: ...Chapter 10 Appendix 464 ...
Страница 478: ......
Страница 479: ......