175
(13) Teaching mode command (MODE) PLC Output Signal
Teaching mode signal (MODES) PLC Input Signal
Operation
Mode
Positioner 1
Simple Direct
Direct numeric
specification
Positioner 2
Positioner 3
Positioner 5
{
:
Equipped
×
:
Not equipped
{
×
×
{
×
×
When the MODE signal is turned ON, the normal operation mode is changed to the teaching
mode.
When the mode is changed to the teaching mode, the MODES Signal is turned ON.
After confirming that the MODES signal is turned ON on the PLC side, start the teaching
operation.
(Note) In order to change the normal operation mode to the teaching mode, the following
conditions are required.
•
The actuator operation (motor) is stopped.
•
The + JOG (JOG+) signal and – JOG (JOG-) signal are turned OFF.
•
The Position Data Import Command (PWRT) Signal and Positioning Start (CSTR) Signal
are turned OFF.
(Note) When the PWRT signal is not turned OFF, the mode is not returned to the normal
operation mode.
(14) Position data import command (PWRT) PLC Output Signal
Position data import complete (WEND) PLC Input Signal
Operation
Mode
Positioner 1
Simple Direct
Direct numeric
specification
Positioner 2
Positioner 3
Positioner 5
{
:
Equipped
×
:
Not equipped
{
×
×
{
×
×
The PWRT signal is available when the teaching mode signal (MODES) is turned ON.
Turn ON the PWRT signal
(Note1)
, Then, the current position data will be written in the position
data box for the position No. set using the PLC's specified Position No. channel.
(Note2)
When the data writing is completed, the WEND signal is turned ON.
After the WEND signal is turned ON, turn OFF the PWRT signal in the host machine.
When the PWRT signal is turned OFF before the WEND signal is turned ON, the WEND
signal is not turned ON.
When the PWRT signal is turned OFF the WEND signal is also turned OFF.
Note1 Turn it ON for 20msec or more. If the time is shorter than 20msec, the writing is not
completed.
Note2 When the data items except for the position have not been defined, the parameter
initial values are written. [Refer to Chapter 8 Parameter]
MODES
(MCON → PLC)
20msec or more
PWRT
(PLC → MCON)
WEND
(MCON → PLC)
3.7 Control and Functions of Input and Output Signals of Modes Other than Remote I/O Mode
Содержание MCON-C
Страница 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Страница 2: ......
Страница 22: ...12 International Standards Compliances MCON with the following overseas standard RoHS Directive CE Marking UL ...
Страница 48: ...38 Chapter 1 Specifications Check ...
Страница 264: ...254 Note 1 blinking Note 2 single flash Note 3 double flash Timing of LED flashing 3 10 Fieldbus Status LEDs ...
Страница 268: ...258 3 10 Fieldbus Status LEDs ...
Страница 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Страница 278: ...268 Chapter 5 Collision Detection Feature ...
Страница 284: ...274 Chapter 6 Power saving Function ...
Страница 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Страница 358: ...348 Chapter 9 Troubleshooting ...
Страница 368: ...358 4 TP adapter and accessories 1 TP adapter external dimensions RCB LB TGS Chapter 10 Appendix ...
Страница 474: ...Chapter 10 Appendix 464 ...
Страница 478: ......
Страница 479: ......