
313
[54] Monitoring period (Parameter No.113)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
113 Monitoring Period
FMNT
msec
1 to 60000
1
This is the parameter to set up the frequency to the initial setting
(Note 1)
of time to obtain data
(Sampling Frequency) when the monitoring mode is selected.
By setting the value in this parameter bigger, the frequency of data obtaining can be made
longer.
It is set to 1msec in the initial setting. Up to 60000msec can be set.
1msec frequency setting
60000msec frequency setting
Up to 2.048 seconds in 4CH
record mode
Up to 34 hours 8 minutes in 4CH
record mode
Up to 1.024 seconds in 8CH
record mode
Up to 17 hours 4 minutes in 8CH
record mode
Up to 4.096 seconds in 2CH
record mode
Up to 68 hours 16 minutes in 2CH
record mode
Note 1 The sampling period can be changed in the RC PC software.
Chapter 8 Parameter
Содержание MCON-C
Страница 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Страница 2: ......
Страница 22: ...12 International Standards Compliances MCON with the following overseas standard RoHS Directive CE Marking UL ...
Страница 48: ...38 Chapter 1 Specifications Check ...
Страница 264: ...254 Note 1 blinking Note 2 single flash Note 3 double flash Timing of LED flashing 3 10 Fieldbus Status LEDs ...
Страница 268: ...258 3 10 Fieldbus Status LEDs ...
Страница 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Страница 278: ...268 Chapter 5 Collision Detection Feature ...
Страница 284: ...274 Chapter 6 Power saving Function ...
Страница 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Страница 358: ...348 Chapter 9 Troubleshooting ...
Страница 368: ...358 4 TP adapter and accessories 1 TP adapter external dimensions RCB LB TGS Chapter 10 Appendix ...
Страница 474: ...Chapter 10 Appendix 464 ...
Страница 478: ......
Страница 479: ......