174
(11) Jog-speed/inch-distance switching (JVEL) PLC Output Signal
Operation
Mode
Positioner 1
Simple Direct
Direct numeric
specification
Positioner 2
Positioner 3
Positioner 5
{
:
Equipped
×
:
Not equipped
{
{
{
{
×
{
It is a signal to switch the parameters to indicate the speed or inching (incremental) distance
when in JOG operation and inching operation. Table below shows the relations.
JVEL
signal
Jog operation : JISL=OFF
Inch operation : JISL=ON
OFF
Parameter No.26, “Jog speed”
Parameter No.26, “Jog speed”
Parameter No.48, “Inch distance”
ON
Parameter No.47, “Jog speed 2”
(Note 1)
Parameter No.47, “Jog speed 2”
Parameter No.49, “Inch distance
2”
Note 1 It will operate in the indicated following speed in the direct indication mode.
When Command Speed Setting = 0 : Operation will be made with a value in
Parameter No. 47 “PIO JOG Speed 2” in
MCON.
When Command Speed Setting
≠
0 : Operation will be made with the setting
value in Command Speed.
(12) Jog/inching switching (JISL) PLC Output Signal
Operation
Mode
Positioner 1
Simple Direct
Direct numeric
specification
Positioner 2
Positioner 3
Positioner 5
{
:
Equipped
×
:
Not equipped
{
{
{
{
×
{
This signal changes over the jog operation and the inching (incremental) operation.
JISL = OFF : Jog operation
JISL = ON : Inching operation
When the JISL signal is turned ON (for inching operation) during the jog operation, the
actuator is decelerated and performs the inching operation.
When the JISL signal is turned OFF (jog) while the actuator is moving by inching, the
actuator will complete the movement and then switch to the jog function.
Jog operation
Inching operation
JISL
OFF
ON
Speed
Parameter No.26, “Jog speed”
Parameter No.26, “Jog speed”
Movement
distance
–
Parameter No.48, “Inch distance”
JVEL
= OFF
Acceleration/
deceleration
Rated value (The specific value varies
depending on the actuator.)
Rated value (The specific value varies
depending on the actuator.)
Speed
Parameter No.47, “Jog speed 2”
(Note 2)
Parameter No.47, “Jog speed 2”
Movement
distance
–
Parameter No.49, “Inch distance 2”
JVEL
= ON
Acceleration/
deceleration
Rated value (The specific value varies
depending on the actuator.)
Rated value (The specific value varies
depending on the actuator.)
Operation
When the JOG +/JOG – signal is ON. Upon detection of the leading (ON edge)
of the JOG +/JOG - signal.
Note 1 It will operate in the indicated following speed in the direct indication mode.
When Command Speed Setting = 0 : Operation will be made with a value in Parameter
No. 47 “PIO JOG Speed 2” in MCON.
When Command Speed Setting
≠
0 : Operation will be made with the setting value in
Command Speed.
3.7 Control and Functions of Input and Output Signals of Modes Other than Remote I/O Mode
Содержание MCON-C
Страница 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Страница 2: ......
Страница 22: ...12 International Standards Compliances MCON with the following overseas standard RoHS Directive CE Marking UL ...
Страница 48: ...38 Chapter 1 Specifications Check ...
Страница 264: ...254 Note 1 blinking Note 2 single flash Note 3 double flash Timing of LED flashing 3 10 Fieldbus Status LEDs ...
Страница 268: ...258 3 10 Fieldbus Status LEDs ...
Страница 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Страница 278: ...268 Chapter 5 Collision Detection Feature ...
Страница 284: ...274 Chapter 6 Power saving Function ...
Страница 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Страница 358: ...348 Chapter 9 Troubleshooting ...
Страница 368: ...358 4 TP adapter and accessories 1 TP adapter external dimensions RCB LB TGS Chapter 10 Appendix ...
Страница 474: ...Chapter 10 Appendix 464 ...
Страница 478: ......
Страница 479: ......