[37] Default acceleration/deceleration mode (Parameter No.52)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
52 Default Acceleration/
Deceleration Mode
MOD
-
0 to 2
0 (Trapezoid
)
When a target position is written to an unregistered position table, this value is automatically set
as the “Acceleration/deceleration mode” of the applicable position number.
Refer to [3.3 Position Data Setting 11) Acceleration/Deceleration Mode] for
Acceleration/Deceleration Mode
Set Value
Description
0
Trapezoid
1
S-motion
2
Primary delay filter
[38] Default stop mode (Parameter No.53)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
53 Default Stop Mode
HSTP
-
0 to 3 (Other than pulse motor
specification)
0 to 7 (Pulse motor specification)
0 (Not applicable)
This parameter defines the power-saving function.
[Refer to 6.1 Automatic Servo-off and Full Servo Functions.]
[39] Current control width number (Parameter No.54)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
54 Current Control Width Number
CLPF
-
0 to 15
In accordance
with actuator
This parameter is for the manufacturer’s use only to determine the response capability of
thecurrent loop control. Therefore, do not change the settings in this parameter. If the
parameter ischanged carelessly, control safety may be adversely affected and a very
dangerous situationmay result.
[40] Position command primary filter time constant (Parameter No.55)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
55 Position Command Primary Filter
Time Constant
PLPF
msec
0.0 to 100.0
0.0
This is to be used when setting the value in “Acceleration/Deceleration Mode” box in the
position table to 2 “Primary Delay Filter”.
The primary delay filter is disabled if “0” is set.
The greater the setting value is, the longer the delay is and the slower the
acceleration/deceleration is. The impact at the acceleration and deceleration will be eased, but
the cycle time will become longer.
Velocity
Time
For servo motor type and
brushless DC motor type only
Chapter 8 Parameter
Содержание MCON-C
Страница 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Страница 2: ......
Страница 22: ...12 International Standards Compliances MCON with the following overseas standard RoHS Directive CE Marking UL ...
Страница 48: ...38 Chapter 1 Specifications Check ...
Страница 264: ...254 Note 1 blinking Note 2 single flash Note 3 double flash Timing of LED flashing 3 10 Fieldbus Status LEDs ...
Страница 268: ...258 3 10 Fieldbus Status LEDs ...
Страница 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Страница 278: ...268 Chapter 5 Collision Detection Feature ...
Страница 284: ...274 Chapter 6 Power saving Function ...
Страница 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Страница 358: ...348 Chapter 9 Troubleshooting ...
Страница 368: ...358 4 TP adapter and accessories 1 TP adapter external dimensions RCB LB TGS Chapter 10 Appendix ...
Страница 474: ...Chapter 10 Appendix 464 ...
Страница 478: ......
Страница 479: ......