[19] Default movement direction for excitation-phase signal
detecting movement (Parameter No.28)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
28 Default Movement Direction for
Excitation-phase Signal Detection PHSP
–
0 : Reversed
direction
1 : Forward
direction
In accordance
with actuator
Excitation detection
(Note)
starts when the servo is turned ON for the first time after the power is
supplied. Define the detection direction at this time.
Even though it is generally unnecessary to change this setting, set this to the direction which
the motor is easy to move when the actuator interferes with the mechanical end or peripheral
object at the time the power is supplied.
If the direction not interfering is the same direction as the home return direction, set the same
values as set to Parameter No.5 Home Return Direction. If the direction is opposite, set the
other values from Parameter No.5. (If No.5 is 0, set 1. If No.5 is 1, set 0.)
Note 1 For Simple Absolute Type, the excitation detection is performed at the end of home
return operation.
[20] Excitation-phase signal detection time (Parameter No.29)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
Specifications
1 to 999
10
Pulse motor
type
29 Excitation-phase Signal
Detection Time
PHSP
msec
50 to 999
128
Servo motor
type
Excitation detection
(Note)
starts when the servo is turned ON for the first time after the power is
supplied. Define the detection direction at this time.
Even though it is generally unnecessary to change this setting, changing the setting of this
parameter may be effective when excitation error is generated or abnormal operation is
confirmed.
Please contact us in the case a change is necessary to this parameter.
Note 1 For Simple Absolute Type, the excitation detection is performed at the end of home
return operation.
For servo motor type and
pulse motor type only
For servo motor type and
pulse motor type only
Chapter 8 Parameter
Содержание MCON-C
Страница 1: ...MCON C CG Controller Instruction Manual Fourth Edition ...
Страница 2: ......
Страница 22: ...12 International Standards Compliances MCON with the following overseas standard RoHS Directive CE Marking UL ...
Страница 48: ...38 Chapter 1 Specifications Check ...
Страница 264: ...254 Note 1 blinking Note 2 single flash Note 3 double flash Timing of LED flashing 3 10 Fieldbus Status LEDs ...
Страница 268: ...258 3 10 Fieldbus Status LEDs ...
Страница 274: ...264 Chapter 4 Vibration Suppress Control Function ...
Страница 278: ...268 Chapter 5 Collision Detection Feature ...
Страница 284: ...274 Chapter 6 Power saving Function ...
Страница 292: ...282 Chapter 7 Absolute Reset and Absolute Battery ...
Страница 358: ...348 Chapter 9 Troubleshooting ...
Страница 368: ...358 4 TP adapter and accessories 1 TP adapter external dimensions RCB LB TGS Chapter 10 Appendix ...
Страница 474: ...Chapter 10 Appendix 464 ...
Страница 478: ......
Страница 479: ......