EXPERT Standard Series User Manual
61
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F6.24
AO1 output function
selection
0:Output frequency (0~F1.06)
1:Reserved
2:Setting frequency (0~F1.06)
3:Output current(0~2* drive rated
current)
4:Output current(0~2* Motor rated
current)
5:Output torque(0~2*Tem)
6:Output voltage (0~1.2*Ve)
7:DC Bus voltage (0~800V)
8:AI1(0~10V/0~20mA)
9:AI2(0~10V/0~20mA)
10:Output power(0~2*Pe)
11:Upper computer percentage(0~
65535)
12: AI3(-10V~10V)
1
0
○
F6.25
Expansion card AO2
output function
selection
1
3
○
F6.26
Analog output range
selection
LED units digit:AO1 bias selection
0:0~10V or 0~20mA
1:2~10V or 4~20mA
LED tens digit:Expansion card AO2
bias selection
0:0~10V or 0~20mA
1:2~10V or 4~20mA
1
00
○
F6.27
AO1 output gain
0.0~200.0%
0.1% 100.0%
○
F6.28
Expansion card AO2
output gain
0.0~200.0%
0.1% 100.0%
○
F6.29
Analog output
voltage current type
selection
LED digit:AO1 output type selection
0:Voltage
1:Current
LED ten digit:Expansion card AO2
output type selection
0:Voltage
1:Current
1
00
○
F6.30
Common IO filtering
time
0.000~10.000s
0.001s 0.002s
○
F6.31
Reserved
-
-
-
○
F6.32
Expansion card DI10
input function
selection
Same function code with F6.00
1
0
○
F6.33
Expansion card DO3
output function
selection
Same function code with F6.11
1
0
○