EXPERT Standard Series User Manual
50
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F1.02
Frequency given
channel selection
0:Digital setting 1, keypad ▲ ▼
regulating
1:Digital setting 2, terminal UP/DN
regulating
2:Digital setting 3, serial port setting
3:AI1 setting
4:AI2 setting
5:Terminal pulse setting
6:Reserved
7:AI3(Expansion card)
1
0
○
F1.03
Numerical frequency
control
LED units digit:
0:Setting frequency power off
storage
1:Setting frequency power off
no storage
LED tens digit:
0:Stop setting frequency
keeping
1:Stop setting frequency
recovery
1
00
○
F1.04
Torque limit selection 0~7
1
0
×
F1.05
Torque limit initial
value
0.0~100.0%
0.1
100%
×
F1.06
Maximum output
frequency
F1.09~550.00Hz
0.01Hz 50.00Hz
×
F1.07
Operation frequency
digit setting
Upper limiting frequency~lower
limiting frequency
0.01Hz 50.00Hz
○
F1.08
Model selection
0:G type
1:P type
1
0
×
F1.09
Upper limiting
frequency
Lower limiting frequency~maximum
frequency
0.01Hz 50.00Hz
○
F1.10
Lower limiting
frequency
0.00~upper limiting frequency
0.01Hz 0.00Hz
○
F1.11
Acceleration time 1
0.1~600.0
Note: default unit second; refer to
FC.09 for units of acceleration and
deceleration time selection
0.75-11kw:6.00s
15kw-55kw:20.00s
75kw-90kw:60.00s
110kw and above:120.00s
0.1s
6.0s
○
F1.12
Deceleration time 1
F1.13
Reserved
F1.14
Reserved
F1.15
Reserved
F1.16
Reserved