EXPERT Standard Series User Manual
100
F1.01
Run command channel
selection
0~2
0
0: Keyboard control valid
Run commands to control the run and stop of the drive by operating keys such as
RUN, STOP/RESET, M-F etc. on the keyboard.
1: Terminal control is valid
The run commands of the drive are controlled by the on and off of external
multi-function terminals (the corresponding multi-function terminals must have the
corresponding functions defined by F6 parameter group).
2: Communication control is valid
The run commands are given by the upper computer communication.
F1.02
Frequency given channel
selection
0~7
0
0: Digital given 1, adjust at operation panel.
1: If digital given is 2, the multi-function terminal sets the UP/DN to adjust frequency.
The initial set value is F1.07, which is adjusted by multi-function terminal UP/DN.
2: If digital given is 3, change the set frequency through the serial port frequency
setting command.
3: AI1 analog given (AI1-GND) frequency setting is determined by AI1 terminal analog
voltage/current, and the input range is: DC 0~10V or DC 0~20mA (selected by F5.12
function code).
4: AI2 analog given (AI2-GND) frequency setting is determined by AI2 terminal analog
voltage/current, and the input range is: DC 0~10V or DC 0~20mA (selected by F5.12
function code).
5: Terminal pulse given frequency setting is determined by terminal pulse frequency
(input by DI4 and DI5. see definition of function code F6.03~F6.04), and the input pulse
signal specifications are: Voltage range 9~30V; dual phase (when DI4 and DI5 are used
together), frequency range is 0 ~ 50.0kHz, single phase (when DI4 is used), frequency
range is 0~100.0kHz.
6: Reserved
7: Expansion card AI3 analog given (AI3-GND) frequency setting is determined by AI3
terminal analog voltage, and the input range is: DC-10V~10V.
Note: The frequency calculation relationship curves of mode 3~7 are determined
by function code F5.00~F5.11, please refer to Section 6.5.
F1.03
Digital frequency control
00~11
00
Only valid for F1.02=0, 1, 2