When the overload pre-alarm state is valid, the working current of the drive exceeds
the overload detection level and hold time exceeds the overload detection time.
Figure 6-55 Schematic Diagram of Overload Pre-alarm Detection Function
Note:
1. Generally, the overload pre-alarm detection level shall be set below the overload
protection level.
2. Within the overload pre-alarm detection time, after the working current is less than
the overload pre-alarm detection level, the overload pre-alarm detection time in the
machine will recounted.
FA.14
Protection action selection
1
0000~3211
0001
FA.15
Protection action selection
2
0000~1113
0001
Under some abnormal conditions, the drive can shield the fault alarm and stop by
setting protection action selection (FA.14 and FA.15), and keep running.
FA.14 defines the protection action selection of undervoltage state and automatic
reset interval.