Note: When pulse feedback is used for speed control, and analog signal is used as
given quantity, the analog given 10V(20mA) corresponds to the synchronous speed
n
0
(
P
f
n
max
0
120
) of the motor.
F8.02
Feedback
channel
selection
0~7
0
0: Input by AI1 analog (the input acquisition type is set by function code F5.12)
1: Input by AI2 analog (the input acquisition type is set by function code F5.12)
2: AI1+AI2
3: AI1-AI2
4: Min{AI1, AI2}
5: Max{AI1, AI2}
When the current input is selected, it is internally converted to a voltage quantity, and
its relationship is: Volt value = milliampere value/2;
6: Pulse: It can be used as PG closed-loop single-phase feedback or two-phase
feedback. Please refer to the definitions of multi-function input terminals DI4 and DI5
(terminal functions of F6.03~F6.04).
7: AI3 (expansion card)
F8.03
Given channel filter time
0.001~50.000s
0.500s
F8.04
Feedback channel filter
time
0.001~50.000s
0.100s
The external given signal and feedback signal often overlap a certain interference. The
channel is filtered by setting the filter time constants F8.03 and F8.04. The longer the filter
time, the stronger the anti-interference ability, but the response becomes slower; the faster
the filter time, the faster the response, but the anti-interference ability weakens.
F8.05
Given
quantity
digital
setting
0.00~10.00V
0.00