1: Free stop
After receiving the stop command, the drive immediately stops the output, and the load
stops freely according to the mechanical inertia.
2: Decelerate and stop + DC brake
After receiving the stop command, the drive reduces the output frequency according to
the deceleration time, and starts the DC braking when reaching the stop braking start
frequency. The output voltage and frequency are shown in Figure 6-11.
Figure 6-11 Schematic Diagram of Decelerate and Stop + DC Braking
See the definitions in F2.09~F2.12 for functions related to stop DC braking
Output frequency
Stop braking time
DC braking quantity
Stop braking wait time
Stop braking start frequency
Run command
Output voltage
(valid value)