③ For speed closed-loop, it is required to determine the speed closed-loop given and
encoder revolution (F8.06~F8.07);
④ Determine the closed-loop regulation characteristics, and if the relationship
between the given and required motor speed is negative, set the closed-loop
characteristics regulation to negative action (F8.16=1);
⑤ Set the integral regulation selection and closed-loop preset frequency function
(F8.17~F8.19);
⑥ Adjust the closed-loop filter time, sampling period, deviation limit and gain
coefficient (F8.12~F8.15).
F8.00
Closed-loop
operation
control selection
0~1
0
0: Closed-loop operation control invalid
1: Closed-loop operation control valid
F8.01
Given channel selection
0~2
0
0: Digital given
Take the value of F8.05 (when set to analog feedback closed-loop, that is, F8.02=0~
5);
Take the value of F8.06 (when set to pulse feedback closed-loop, that is, F8.02=6).
1: Given by AI1 analog (the input acquisition type is set by function code F5.12)
2: Given by AI2 analog (the input acquisition type is set by function code F5.12)