EXPERT Standard Series User Manual
187
decelerates smoothly and the running current is small, but the deceleration time becomes
longer.
FC.03
Automatic energy-saving
operation
0~1
0
0: Do not act
1: Action
During the no-load or light-load operation, the motor detects the load current and
adjusts the output voltage appropriately to achieve the purpose of energy saving.
Note: This function is especially effective for fan pump loads.
FC.04
Slip compensation gain
0.0%~200.0%
0.0%
FC.05
Slip compensation limit
threshold
0.0%~250.0%
100.0%
FC.06
Slip compensation filter
time
0.0~25.0s
2.0
Figure 6-59 Automatic Slip Compensation