EXPERT Standard Series User Manual
167
In the closed-loop given channels, except for the three channels defined in F8.01, the
voltage value of multistage closed-loop given defined in F8.20~F8.34 can also be used as
closed-loop given.
The voltage selection of multistage closed-loop given 1~15 can realize flexible
switching through external terminals, refer to terminal functions of 30~32 and 52 in F6.00~
F6.09 and F6.32. It can also be used with simple PLC closed-loop section, see group F9
function code description.
F8.35
Closed-loop output polarity
selection
0x721
0x100
Unit digit:
0: Closed-loop output is negative, run at zero-frequency.
1: If the closed-loop output is negative, reverse, but if reversal is prohibited by
F2.30, the drive runs at the lower limit frequency.
Ten digit:
0: PID upper and lower limits keep unchanged.
1: PID upper and lower limits are determined by AI.
2. PID upper and lower limits are determined by FC.27.
4. PID upper and lower limits are determined by FD.13 and FD.14.
Hundred digit: This is a special function of wire drawing machine
1. Emergency stop valid
2. Synchronous stop function
4: Jog frequency given switching
F8.36
Closed-loop feedback loss
action selection
0~0x27
0x00
F8.37
Process
closed-loop
feedback loss detection
value
0.0~100.0%
10.0%
F8.38
Process
closed-loop
feedback loss detection
time
0.0~1000.0s
1.0s
F8.36 closed-loop feedback loss action