Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F6.34
Expansion card relay
output RA/RB/RC
Same function code F6.13
1
0
○
F6.35
AO1 zero bias
coefficient
0.0%~100.0%
0.1% 100.0%
*
F6.36
DO Pulse duty cycle 0 ~100
1
50
×
F6.37
AO2 Zero bias
coefficient
0.0% ~100.0%
0.1% 100.0%
×
F7 group Advanced function parameter
F7.00
Overvoltage stall
point
380V Model:110.0~150.0%
220V Model:100.0~130.0%
0.1%
×
F7.01
Overvoltage control
voltage
0.000~9.999v
0.01V 0.10V
×
F7.02
Overvoltage stall
gain Kp1
0~2.00
1
6
×
F7.03
Overvoltage stall
integral time Ki1
0~2.00
1
100
×
F7.04
Overvoltage stall
gain Kp2
0.0~2.00
0.1
4.0
×
F7.05
Overvoltage stall
integral time Ki2
0~2.00
1
10
×
F7.06
Over current stall
level
20.0%~200.0%
0.1% 150.0%
×
F7.07
Over current stall
action selection
0:Constant speed ineffective
1:Constant speed effective
Note:Acceleration and deceleration
is always effective
1
1
×
F7.08
Over current stall
gain Kp
0~99.99
1
6
×
F7.09
Over current stall
integral time
1~2.00
1
100
×
F7.10
Reserved
-
-
-
×
F7.11
Reserved
-
-
-
×
F7.12
Rotational speed
tracking
acceleration
0~100.0S
1
10
×
F7.13
Reserved
-
-
-
×
F7.14
Instantaneous
stop/no stop
function selection
0:No action
1:decelerated
2:Ramp to stop
1
0
×