6.14 Group Fd additional parameter function
Fd.00
DO1 output on delay
0.0~600.0
0.0
Fd.01
DO1 output off delay
0.0~600.0
0.0
Fd.02
DO2 output on delay
0.0~600.0
0.0
Fd.03
DO2 output off delay
0.0~600.0
0.0
Fd.04
Relay output on delay
0.0~600.0
0.0
Fd.05
Relay output off delay
0.0~600.0
0.0
This delay is valid no matter what function is set at the output port.
Fd.06
Overstart overvoltage
coefficient
50.0~200.0%
130.0%
Fd.07
Overvoltage hold time
0.001~20.000s
0.001s
Fd.08
Transition time when
overvoltage is switched to
normal voltage
0.001~5.000s
0.001s
Overstart mode: When F1.17=5, the above functions are valid.
Fd.10
Automatic torque boost
filter factor
0.00~1.00
0.20
The function code is mainly for the automatic torque boost function in V/F mode.
Fd.13
PID upper limit
0.0~100.0%
100.0%
Fd.14
Lower PID limit
0.0~100.0%
100.0%
This function is mainly for the output limit of PID upper and lower limits, which is
related to F8.35 function code. Please refer to F8.35 settings for detailed settings.