Note: The multi-function input terminal can be used to clear the actual length (DIi is
defined to No. 39 function), the normal counting and the actual length calculation can be
performed only after the terminal is disconnected.
The actual length is FC.15, and it is automatically stored during power failure. When
the set length FC.14 is 0, the fixed-length stop function is invalid, but the length calculation
is still valid.
FC.20
Set the running time
0~maximum timing
65.535kh
0
After the accumulated running time reaches the set running time, the drive can output
an indication signal, refer to function introduction of F6.11~F6.13.
U0.37 indicates the cumulative run time of the drive from leaving the factory till now.
FC.21
Reserved
-
-
FC.22
Function
selection
of
restart from power failure
0~1
0
FC.23
Wait time of restart from
power failure
0.0~10.0s
0.5s
This function realizes whether the drive automatically starts running and the wait time
before automatically running under different run command channels when the drive
restarts from power failure.
If FC.22 is set to 0, the drive will not run automatically when restarting after power
failure.
If FC.22 is set to 1, and the conditions for starting are met, the drive will run
automatically after a wait time defined by FC.23 when restarting after power failure.
The setting of this function code, the running state at power failure moment and the
control command state at power on moment jointly determine whether the drive will run
automatically after power on. See Table 6-15.