EXPERT Standard Series User Manual
188
Electric status: When the actual speed is lower than the given speed, gradually
increase the compensation gain (FC.04).
Generation status: When the actual speed is higher than the given speed, gradually
increase the compensation gain (FC.04).
The regulation range of slip compensation is slip compensation limit (FC.05) × rated
slip.
FC.07
Reversal overcurrent stall
compensation
0.0~100.0%
0.0
When the running direction is switched during the drive running, the limit value of
overcurrent stall will be automatically switched to be equal to F7.06+FC0.7.
FC.08
Cooling fan control
0~2
0
0: Run in automatic mode
Note: Continue running for 3 minutes after stop
1: The fan keeps rotating during power-on
2: In running state, when the temperature is higher than 45℃, the fan runs; when the
temperature is lower than 40℃, the fan stops.
FC.09
Acceleration/Deceleration
time unit
0~1
0
This function determines the time unit of acceleration and deceleration.
0: Second
1: Minute
This function is valid for all acceleration and deceleration processes except jog.
Up to 60 hours of acceleration/deceleration time can be set, which is suitable for
occasions requiring long acceleration/deceleration.
Note: It is suggested to select second as the time unit as far as possible.
FC.10
Droop control frequency
0.00~10.00Hz
0.00Hz