EXPERT Standard Series User Manual
156
F7.21
Energy
consumption
braking voltage point
110.0~150.0%
125.0%
For the setting of energy consumption braking/starting voltage point, the set value is a
percentage. When F7.21 is set to 125%, the reference value is the bus voltage
corresponding to the rated voltage 670V of the drive.
F7.22
Overcurrent and current
limiting acceleration limit
0~100.0
90.0
When the overcurrent and current limiting is valid, the acceleration will gradually
decrease. This parameter limits the change range. When it is set to 100, the acceleration
can be reduced to 0; when it is set to 0, the acceleration keeps unchanged.
F7.23
Speed display factor
0.001~9.999
1.000
This function code is used to correct the display error of the speed scale and has no
effect on the actual rotation speed.
F7.24
Linear speed coefficient
0.001~9.999
1.000
This function code is used to correct the scale display error of the linear speed and
has no effect on the actual speed.
F7.25
Closed-loop analog display
coefficient
0.001~9.999
1.000
This function code is used to correct the display error between the actual physical
quantities (pressure, flow, etc.) and the given or feedback quantities (voltage and current)
during closed-loop control, and has no influence on the closed-loop PI adjustment.