EXPERT Standard Series User Manual
180
The overload pre-alarm detection selection (FA.11) defines the relative values of
overload pre-alarm detection selection, alarm action selection and detection level.
Figure 6-54 Overload Detection Settings
Unit digit: Overload pre-alarm detection selection
0: Overload detection keeps working during the drive running.
1: The overload detection works only when the drive runs at a constant speed.
Ten digit: Overload pre-alarm action selection
0: When overload detection is valid, do not alarm and continue running.
1: When the overload detection is valid, alarm and stop.
Hundred digit: Overload pre-alarm detection selection
0: Detection level relative to the rated current of the motor (fault code E008 when
warning).
1: Detection level relative to the rated current of the drive (fault code E008 when
warning).
The overload pre-alarm detection level (FA.12) defines the current threshold of
overload pre-alarm action, and its set value is the percentage relative to the rated current
(see FA.11).
The overload pre-alarm detection time (FA.13) defines the overload pre-alarm signal
output when the drive output current is continuously greater than the overload detection
level (FA.12) for a period of time.