EXPERT Standard Series User Manual
51
Parameter
code
Parameter
name
Setting range
Mini
munit
Default
value
Mod
ition
F1.17
V/F curve setting
0: Linear V/F
1:User setting V/F curve (confirmed
by F1.18~F1.23 function code)
2:Reduced torque characteristic
curve 1(2.0 hypo-power)
3:Reduced torque characteristic
curve 2(1.7 hypo-power)
4:Reduced torque characteristic
curve 3(1.2 hypo-power)
1
0
×
F1.18
V/F frequency value
F1
0.00~F1.20
0.01Hz 12.50Hz
×
F1.19
V/F voltage value V1 0~F1.21
0.1%
25.0%
×
F1.20
V/F frequency value
F2
F1.18~F0.22
0.01Hz 25.00Hz
×
F1.21
V/F voltage value V2 F1.19~ F1.23
0.1%
50.0%
×
F1.22
V/F frequency value
F3
F1.20~F3.04
0.01Hz 37.50Hz
×
F1.23
V/F voltage value V3 F1.21~100.0%
0.1%
75.0%
×
F1.24
Running direction
setting
0:Forward
1:Reversal
1
0
○
F1.25
Carrier frequency
setting
1~15kHz
0.75-11kw:6kHz
15kw-55kw:4kHz
75kw-90kw:3kHz
110kw and above: 2kHz
1kHz
○
F1.26
Carrier frequency
automatic
adjustment selection
0:Invalid
1:effective
1
1
○
F2 group Start/stop control
F2.00
Starting mode
LED digits:Start mode
0:Start from start frequency
1:DC braking and start from start
frequency
2:Rotate speed tracking
LED ten digits:Rotate speed tracking
way
0:tracking from stop frequency
1:tracking from maximum frequency
1
00
×
F2.01
Start frequency
0.20~60.00Hz
0.01Hz 0.50Hz
○