EXPERT Standard Series User Manual
142
Including:
SB1: Stop button
SB2: Run button
DIx is the multi-function input terminal of DI1~DI2, in this case, its corresponding
terminal function shall be defined as function 16 “three-wire operation control". Terminal
function corresponding to DIx(FWD) is defined as function 36, and terminal function
corresponding to DIx(REV) is defined as function 37.
Note: In terminal control mode, for two-wire operation modes 1 and 2, although the
terminal level is valid, when the stop command is generated by other sources to stop the
drive, even if the control terminal defined as FWD/REV is still valid, no run command will be
generated. To rerun the drive, you need to trigger it again. For example, terminal functions
11 and 35 (see F6.00), PLC single-cycle stop, fixed-length stop, and valid STOP/RESET
key stop under terminal run command channel (see FC.31). Things are different for the
fault alarm stop. If reset fault when the control terminal defined as FWD/REV is valid, the
drive will not start.
F6.10
UP/DN rate
0.01~99.99Hz/s
1.00Hz/s
This function code defines the change rate of the set frequency modified by the UP/DN
terminal.
F6.11
Open
collector
output
terminal DO1
0~19
0
F6.12
Open collector output
terminal DO2
0~32
1
F6.13
Relay output function
selection (TA/TB/TC)
0~19
16
The output characteristics of open collector output terminals DO1 and DO2 and relay
output terminal are described in Section 3.5 of Chapter 3. Table 6-10 list the options for the
above three function parameters, and the same output terminal function is allowed to be
selected repeatedly.