EXPERT Standard Series User Manual
230
Application examples
The command to start 1#drive for forward rotating, and to set the rotational speed
at 50.00HZ (which is 5000 internally) is as follows:
Address Functio
n Code
Register
Address
Register
Number
Register
Content
Bytes
Register
Content Checksum
Request 0x01
0x10
0x3200
0x0002
0x04
0x01C7,0x
1388
0x0399
Respon
0x01
0x10
0x3200
0x0002
None
None
0x4F70
1#drive parks at the quickest speed:
Address
Function Code
Register
Address
Register
Content
Checksum
0x01
0x06
0x3200
0x00C3
0xC723
0x01
0x06
0x3200
0x00C3
0xC723
5#drive Jog rotates forward:
Address
Function Code
Register
Address
Register
Content
Checksum
0x05
0x06
0x3200
0x00D0
0x876A
0x05
0x06
0x3200
0x00D0
0x876A
5#drive Jog stops:
Address
Function Code
Register
Address
Register
Content
Checksum
0x05
0x06
0x3200
0x00C0
0x86A6
0x05
0x06
0x3200
0x00C0
0x86A6
5# drive fault resets:
Address
Function Code
Register
Address
Register
Content
Checksum
0x05
0x06
0x3200
0x0280
0x86C6
0x05
0x06
0x3200
0x0280
0x86C6