EXPERT Standard Series User Manual
150
LED digits refer to the thousand, hundred, ten or unit digits displayed by LED on the
operation panel.
Note: The factory settings of all terminals are positive logic。
F6.24
AO1 terminal output
function selection
0~12
0
F6.25
AO2 terminal output
function selection
0~12
3
AO1 and AO2 are analog output terminals.
See Section 3.5 of Chapter III for the output characteristics of AO1 and AO2, and the
analog output range is determined by function code F6.26.
The linear corresponding relationship between the output of AO1 and AO2 and the
indication range is shown in Table 6-14.
Table 6-14 Output Terminal Indication
Contents
Corresponding function
Indication range
0
Output frequency
0~maximum operation
frequency
1
Reserved
Reserved
2
Set frequency
0~maximum operation
frequency
3
Output current
0~2 times drive rated current
4
Output current
0~2 times motor rated current
5
Output torque
0~2 times rated motor torque
6
Output voltage
0~1.2 times drive rated
voltage
7
Bus voltage
0~800V
8
AI1
0~10V/0~20mA
9
AI2
0~10V/0~20mA
10
Output power
0~2 times rated power
11
Upper computer extended
function 2
0~1000
12
AI3 (expansion card)
-10~10V